Cables for use in ATEX or IEC applications, Zone 1 and 2
Read this First
Instrumentation Cables;
BS5308
These cables are for instrumentation applications. Designed
for on-shore use, they are made with PVC or Polyethylene
insulations, and PVC outer sheaths. They are available with or
without a galvanized steel wire armor for protection in harsh
environments. For Zone 1 and 2 applications, per EN 60079-14,
these cables must meet the flame retardance specifications of
IEC60332. For data sheets click here.
BS 6883
These cables are for instrumentation, control, and power applications.
Designed for rugged use, they are typically made with EPR
insulation, SW4 outer sheath, and with or without a galvanized
steel wire braid for harsh environments. For Zone 1 and 2
applications, per EN 60079-14, these cables must meet the flame retardance specification of IEC60332.
For data sheets click here.
BS7917
These cables
are very similar to BS6883 but also meet the IEC60331 fire resistant
specification. Each conductor is insulated with MICA glass
tape and are used where circuit integrity is critical.
For
data sheets click here.
NEK 606
RFOU (i) 250V
These
instrument cables are considered world class cables. The are
flame retardant to IEC-60332-3-22. Designed for rugged
off-shore applications, they have a EPR insulation, flame retardant
halogen-free thermoset compound bedding, a tinned copper wire braid
and flame retardant halogen-free and mud resistant thermoset
compound. For data sheets click here.
BFOU (i) 250V
These cables
are the same as RFOU except they also meet the fire resistant
specification of IEC-60331.
For data sheets click here.
Power and Control Cables
BS 6883
These cables are for instrumentation, control, and power applications.
Designed for rugged use, they are typically made with EPR
insulation, SW4 outer sheath, and with or without a galvanized
steel wire braid for harsh environments. For Zone 1 and 2
applications, per EN 60079-14, these cables must meet the flame retardance specification of IEC60332.
For data sheets click here.
BS5467
These cables are for power and control applications. Designed
for on-shore use, they are made with PVC or XLPE insulations, and
either PVC or EPR outer sheaths. They are available with
or without a galvanized steel wire armor for protection in harsh
environments. For Zone 1 and 2 applications, per EN 60079-14,
these cables must meet the flame retardance specifications of
IEC60332. For data sheets click here.
BS6724
These cables
are are very similar to BS5467 cables but are zero halogen.
Designed for on-shore use, they are
made with LSF inner sheath, Type LTS1 to BS7655 and
black LSF outer sheath Type LTS1 to BS7655. They are available with
or without a galvanized steel wire armor for protection in harsh
environments. For Zone 1 and 2 applications, per EN 60079-14,
these cables must meet the flame retardance specifications of
IEC60332. For data sheets click here.
NEK 606
RFOU 0.6/1kV
These
power and control cables are halogen-free and mud resistant.
They are fire retardant to IEC 60332, have an EPR insulation and a
tinned copper wire braid.
For data sheets click here.
BFOU 0.6/1kV
These
cable are the same as the RFOU but also meet the fire resistant
specification of IEC 60331.
For data sheets click here.
Cables for use
in Class I, Division 1 and 2, Zone 1 and 2 Locations
Class I, Division 1 or Zone 1
Type MC-HL
These cable are for power, control and instrumentation.
Designed for rugged use, they are typically made with XLPE or
PVC insulations,
a continuous aluminum armor and a PVC outer sheath. For
use in Division 1 and 2 locations, these cable must be third party
certified and marked "MC-HL".
For data sheets click
here.
Type ITC-HL
These instrument cables are almost identical to the MC-HL instrument
cables except the are rated 300 volts.
For data sheets click
here.
Type MI cable
MI cable typically has a copper sheath and conductors with a
magnesium oxide insulation. The cable is provided with it's
own cable gland and terminating system. The insulation of
these cables are very hydroscopic and termination of the glands is
extremely important to keep moisture out. Ex Industries does
not sell these cables and we do not provide data sheets.
Class I, Division 2 or Zone 2
All cables allowed for use in Class
1, Division 1 or Zone 1 locations
Type PLTC cables
These cables are very similar to ITC-HL cable but are only listed
for Class I, Division 2 applications.
For data sheets click
here.
Type ITC cables
These cables are very similar to ITC-HL cable but are only listed for
Class I, Division 2 applications.
For data sheets click here.
Type MC, MV and TC cables
Type MC cable is control and power cable approved
for Class I, Division 2 applications. These cable must me
terminated with approved fittings. Installation of these cable
must also adhere to NEC Type MC and UL Standard 1569. For data
sheets contact Ex Industries.
Type TC cables are instrument, control and power cables for
use in tray cable and is suitable for Class I, Division 2
applications. These cables must be terminated with approved
fittings. Installation of these cable must also adhere to NEC
articles 336, 392 and 501,and Class I circuits per NEC article 725.
For data sheets contact Ex Industries.
Type MV cable is 5KV medium voltage power cable
approved for Class I, Division 2 applications. These cable
must me terminated with approved fittings. Contact Ex
Industries for data sheets.
Click here for a list of common terms and abbreviations that are
used.
Table of Comparisons
AWG/mm2
| AWG |
Approx.
mm2 |
| 18 |
0.75 |
| 16 |
1.5 |
| 14 |
2.5 |
| 12 |
4.0 |
| 10 |
6.0 |
| 8 |
10.0 |
| 6 |
16.0 |
| 4 |
25.0 |
| 2 |
35.0 |
| 1/0
or 0 |
50.0 |
| 2/0
or 00 |
70.0 |
| 3/0
or 000 |
95.0 |
| 4/0
or 0000 |
- |
| 250
kcmils |
120.0 |
| 300
kcmils |
150.0 |
| 400
kcmils |
185.0 |
| 500
kcmils |
240.0 |
| 600
kcmils |
300.0 |
| 1000
cmils |
500.0 |
|