| What cable gland do I
use? This is often a very confusing issue. Below is a
cable by cable list with the glands you should use depending on what
cable you chose and it's application. Be sure to read the
application information and then scroll down to the cable you are
planning to use.
We start with IEC cables. The below information
should only be applied to IEC cables for use in IEC or ATEX
applications.
When terminating to increased safety enclosures, type "e"
protection must be maintained but compound filled glands are not
required. We quite often use a gland that is dual rated Ex de
(flameproof and increased safety).
When terminating to a flameproof enclosure and the cable does not
meet EN60079-14 b) of 10.4.2 a
compound gland must be used. If the cable does meet
EN60079-14,
10.4.2 then the
"Selection Chart
Figure 1" must be used.
Click on the Hawke Cable series
for a data sheet.
Instrumentation Cables
BS5308 Part 1/2 Type 1 (all screening options)
When terminating to an Increased Safety enclosure the cable gland
shall maintain a minimum protection type "e" and should maintain the IP rating
of enclosure. Use a Hawke
501/421 series
cable gland.
When terminating to a Flameproof enclosure a compound filled gland
must be used and shall maintain type "d" protection. Use a Hawke
ICG/623
series cable gland.
BS5308 Part 1/2 Type 2 (all screening options)
When terminating to an Increased Safety enclosure the cable gland
shall maintain a minimum protection type "e" and should maintain the IP rating
of the enclosure. Use a Hawke
501/453
series
cable gland.
When terminating to a Flameproof enclosure a compound filled gland
must be used and shall maintain type "d" protection. Use a Hawke
ICG/653
series cable gland.
BS5308 Part 2/2 Type 1 (all screening options)
When terminating to an Increased Safety enclosure the cable gland
shall maintain a minimum protection type "e" and should maintain the IP rating
of enclosure. Use a Hawke
501/421 series
cable gland.
When terminating to a Flameproof enclosure a compound filled gland
must be used and shall maintain type "d" protection. Use a Hawke
ICG/623
series cable gland.
BS5308 Part 2/2 Type 2 (all screening options)
When terminating to an Increased Safety enclosure the cable gland
shall maintain a minimum protection type "e" and should maintain the IP rating
of the enclosure. Use a Hawke
501/453
series
cable gland.
When terminating to a Flameproof enclosure a compound filled gland
must be used and shall maintain type "d" protection. Use a Hawke
ICG/653
series cable gland.
BS6883 Instrumentation (all screening options),
Power and Control Cables terminating to Increased Safety Enclosures.
When terminating to an Increased Safety enclosure the cable gland
shall maintain a minimum protection type "e" and should maintain the IP rating
of the enclosure. When using non-braided cable use a Hawke
501/421
series cable gland. When using a braided cable use a Hawke
501/453 cable gland.
BS6883 Instrumentation (all screening options),
Power and Control Cables terminating to Flameproof Enclosures.
These cables comply with EN60079-14, b) of
10.4.2. When terminating to a Flameproof enclosure use
EN60079-14 the
(Selection Chart Figure 1)
- Selection chart for cable entry devices into flameproof enclosure
to determine if compound filled glands are required. If
compound glands are not required use a Hawke
501/421
for non-braided cables or the Hawke
501/453 for braided cables.
If compound glands are required use the Hawke
ICG/623
glands for cables without a braid and
ICG/653
glands if they have a braid.
BS7917 Instrumentation Cables (all screening options)
when terminating to Increased Safety Enclosures.
When terminating to an Increased Safety enclosure the cable gland
shall maintain a minimum protection type "e" and should maintain the IP rating
of the enclosure. When using non-braided cable use a Hawke
501/421
series cable gland. When using a braided cable use a Hawke
501/453 cable gland.
BS7917 Instrumentation Cables (all screening options)
when terminating to Flameproof Enclosures.
These cables comply with EN60079-14, b) of
10.4.2. When terminating to a Flameproof enclosure use
EN60079-14 the
(Selection Chart Figure 1)
selection chart for cable entry devices into flameproof enclosure
to determine if compound filled glands are required. If
compound glands are not required use a Hawke
501/421
for non-braided cables or the Hawke
501/453 for braided cables.
If compound glands are required use the Hawke
ICG/623
glands for cables without a braid and
ICG/653
glands if they have a braid.
NEK 606
RFOU (i) and BFOU (i) Instrumentation Cables terminating to
Increased Safety Enclosures.
When terminating to an Increased Safety enclosure the cable gland
shall maintain a minimum protection type "e" and should
maintain the IP rating of the enclosure. Use a Hawke
501/453 cable gland.
RFOU (i) and BFOU (i)
Instrumentation Cables terminating to Flameproof Enclosures.
These cables comply with EN60079-14, b) of
10.4.2. When terminating to a Flameproof enclosure use
EN60079-14 the
(Selection Chart Figure 1)
selection chart for cable entry devices into flameproof enclosure
to determine if compound filled glands are required. If
compound glands are not required use the Hawke
501/453.
If compound glands are required use the
ICG/653.
Power and Control Cables
BS5467
When terminating to an Increased Safety enclosure the cable gland
shall maintain a minimum protection type "e" and should maintain the IP rating
of the enclosure. Use a Hawke
501/453
series
cable gland.
When terminating to a Flameproof enclosure a compound filled gland
must be used and shall maintain type "d" protection. Use a Hawke
ICG/653
series cable gland.
BS6724
When terminating to an Increased Safety enclosure the cable gland
shall maintain a minimum protection type "e" and should maintain the IP rating
of the enclosure. Use a Hawke
501/453
series
cable gland.
When terminating to a Flameproof enclosure a compound filled gland
must be used and shall maintain type "d" protection. Use a Hawke
ICG/653
series cable gland.
RFOU and BFOU Power and Control Cables
terminating to Increased Safety Enclosures.
When terminating to an Increased Safety enclosure the cable gland
shall maintain a minimum protection type "e" and should
maintain the IP rating of the enclosure. Use a Hawke
501/453 cable gland.
RFOU and BFOU Power and
Control Cables terminating to Flameproof Enclosures.
These cables comply with EN60079-14, b) of
10.4.2. When terminating to a Flameproof enclosure use
EN60079-14 the
(Selection Chart Figure 1)
selection chart for cable entry devices into flameproof enclosure
to determine if compound filled glands are required. If
compound glands are not required use the Hawke
501/453.
If compound glands are required use the
ICG/653.
The following information is for use with cables in
hazardous locations in North America
Unlike IEC cables, cable for use in North
America are defined in the NEC Article 501, and CSA and must be third party
certified for use in Division I areas. Cables for use in
Division 2 areas are defined but not necessarily certified for hazardous areas.
Instrumentation Cables
Type MC-HL instrumentation cables can
be used in Division 1 or 2 areas. When
terminating into general purpose enclosures in Division 2 areas it
is not required to use
a compound filled gland. The cable gland can be be rated general purpose
but should maintain the NEMA rating of the enclosure. Use the
Hawke type
701 series.
When terminating to an AEx Increased Safety enclosure, type "e"
protection should be maintained and the IP rating of the
enclosure should be maintained. When terminating to an explosionproof enclosure a third party certified Class I, Division 1
compound filed gland should be used. Use a
Hawke type 711
cable gland.
Type ITC-HL instrumentation cables
can be used in Division 1 or 2 areas. When terminating into
general purpose enclosures in Division 2 areas it is not required to
use a compound filled gland. The cable gland can be be rated
general purpose but should maintain the NEMA rating of the enclosure. Use the
Hawke type
701 series.
When terminating to an AEx Increased Safety enclosure, type "e"
protection should be maintained and the IP rating of the
enclosure should be maintained. When terminating to an explosionproof enclosure a third party certified Class I, Division 1
compound filed gland should be used. Use a
Hawke type 711
cable gland.
Type PLTC and ITC instrument cables
are for use in Division 2 areas. When
terminating into general purpose enclosures in Division 2 areas it
is not required to use
a compound filled gland. The cable gland can be be rated general purpose
but should maintain the NEMA rating of the enclosure. Use the
Hawke type
701 series.
When terminating to an explosionproof enclosure a UL Listed compound
gland must be used.
Use the Hawke
type 711 series.
|